Invensys Recalls Siebe Actuators in Building Fire and Smoke Dampers
Invensys is recalling Siebe actuators used in fire and smoke dampers because they can jam and prevent dampers from closing during a fire.
What this means for you
Our assessment, not the agency’s: severity 4/5 (Severe).
The hazard poses a serious risk of illness, injury, or structural failure. Stop using the product immediately and contact the manufacturer for a refund or repair.
Our severity reasoning: The source text explicitly states that if dampers fail to close during a fire, 'serious injury or death can be suffered by building occupants,' which aligns with the rubric criterion for 'significant injury/property-damage reports' or risk of serious harm.
Plain-English summary
Invensys Building Systems is recalling up to 560,000 Siebe actuators, specifically MA-200 and MA-200-1 series models, used in building fire and smoke dampers. These actuators were installed in dampers manufactured by various companies between December 1993 and October 1999 and installed in commercial and residential buildings. The actuators have manufacture date codes ranging from 9348 through 9947.
The recall is due to a defect where the actuators can jam, preventing the dampers from closing during a fire. The dampers are designed to close to limit the spread of smoke, fire, and fumes through a building's ventilation system. If the dampers fail to close, building occupants could suffer serious injury or death. Building owners, damper manufacturers, and fire and safety investigators have reported instances of dampers not closing during testing.
Building owners and managers should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 7 a.m. and 7 p.m. CT, Monday through Friday, to test the actuators. Only actuators that fail testing are eligible for a free replacement. Additional program information is available at www.regcen.com/MA200.
The recalled product
- Product
- Siebe actuators
- Affected units
- 560,000
Distribution
Distributed nationwide across the United States.
Related recalls
Same hazard · fire spread
See all →- High
- SevereInvensys Recalls Siebe Actuators in Building Fire and Smoke Dampers
CPSC · 2002-10-02
Other consumer product recalls
- SevereLithonia Lighting Recalls RSX Luminaires with Adjustable Tilt Arms
CPSC · 2026-10-22
- Severe
- SevereVQQQ Gas Patio Heaters Recalled for Fire and Burn Hazards
CPSC · 2026-10-22
- Severe
- Severe
Similar recalls
- SevereInvensys Recalls Siebe Actuators in Building Fire and Smoke Dampers
CPSC · 2002-10-02
- High
- HighInvensys Recalls TS11 Thermal Safety Control Valves Due to Fire Risk
CPSC · 2002-03-26
- High
- HighChim-A-Lator Air Damper Systems Recall for Burn Hazard
CPSC · 1979-11-06
- High